23-62 Timed Bin Data
Range: Function:
0 N/A* [0 - 4294967295 N/A] Array with 10 elements ([0]-[9] below parameter number in display).
Press OK and step between elements by means of
▲
and
▼
buttons on
the keypad.
10 counters with the frequency of occurrence for the operating data
monitored sorted according to the intervals as for par.23-61
Continuous
Bin Data.
Starts to count at the date/time programmed in par.23-63
Timed Period
Start, and stops at the time/date programmed in par.23-64 Timed Period
Stop. All counters can be reset to 0 in par.23-67 Reset Timed Bin Data.
23-63 Timed Period Start
Range: Function:
0 N/A* [0 - 0 N/A] Set the date and time at which the Trending starts the update of the
Timed Bin counters.
Date format will depend on setting in par.0-71
Date Format, and time
format on setting in par.0-72
Time Format.
Note
The frequency converter has no back up of the clock function and the set date/time will reset to default
(2000-01-01 00:00) after a power down unless a Real Time Clock module with back up is installed. Consequently
the logging will be stopped until date/time is readjusted in par.0-70
Date and Time. In par.0-79 Clock Fault it is
possible to program for a Warning in case clock not has been set properly, e.g. after a power down.
Note
When mounting an Analog I/O MCB 115 option card, a battery back up of the date and time is included.
23-64 Timed Period Stop
Range: Function:
0 N/A* [0 - 0 N/A] Set the date and time at which the Trend Analyses must stop update of
the Timed Bin counters.
Date format will depend on setting in par.0-71
Date Format, and time
format on setting in par.0-72
Time Format.
Note
When mounting an Analog I/O MCB 115 option card, a battery back up of the date and time is included.
23-65 Minimum Bin Value
Range: Function:
0 %* [0 - 100. %] Array with 10 elements ([0]-[9] below parameter number in display).
Press OK and step between elements by means of
▲
and
▼
buttons on
the keypad.
Set the minimum limit for each interval in par.23-61
Continuous Bin Da-
ta and par.23-62 Timed Bin Data. Example: if selecting
counter
[1] and
changing setting from 10% to 12%,
counter
[0] will be based on the in-
terval 0 - <12% and
counter
[1] on interval 12% - <20%.
Parameter Description
TR200 Programming Guide 233