23-62 Timed Bin Data
Range: Function:
0 N/A* [0 - 4294967295 N/A] Array with 10 elements ([0]-[9] below parameter number in display).
Press OK and step between elements by means of
and
buttons on
the keypad.
10 counters with the frequency of occurrence for the operating data
monitored sorted according to the intervals as for par.23-61
Continuous
Bin Data.
Starts to count at the date/time programmed in par.23-63
Timed Period
Start, and stops at the time/date programmed in par.23-64 Timed Period
Stop. All counters can be reset to 0 in par.23-67 Reset Timed Bin Data.
23-63 Timed Period Start
Range: Function:
0 N/A* [0 - 0 N/A] Set the date and time at which the Trending starts the update of the
Timed Bin counters.
Date format will depend on setting in par.0-71
Date Format, and time
format on setting in par.0-72
Time Format.
Note
The frequency converter has no back up of the clock function and the set date/time will reset to default
(2000-01-01 00:00) after a power down unless a Real Time Clock module with back up is installed. Consequently
the logging will be stopped until date/time is readjusted in par.0-70
Date and Time. In par.0-79 Clock Fault it is
possible to program for a Warning in case clock not has been set properly, e.g. after a power down.
Note
When mounting an Analog I/O MCB 115 option card, a battery back up of the date and time is included.
23-64 Timed Period Stop
Range: Function:
0 N/A* [0 - 0 N/A] Set the date and time at which the Trend Analyses must stop update of
the Timed Bin counters.
Date format will depend on setting in par.0-71
Date Format, and time
format on setting in par.0-72
Time Format.
Note
When mounting an Analog I/O MCB 115 option card, a battery back up of the date and time is included.
23-65 Minimum Bin Value
Range: Function:
0 %* [0 - 100. %] Array with 10 elements ([0]-[9] below parameter number in display).
Press OK and step between elements by means of
and
buttons on
the keypad.
Set the minimum limit for each interval in par.23-61
Continuous Bin Da-
ta and par.23-62 Timed Bin Data. Example: if selecting
counter
[1] and
changing setting from 10% to 12%,
counter
[0] will be based on the in-
terval 0 - <12% and
counter
[1] on interval 12% - <20%.
Parameter Description
TR200 Programming Guide 233