0-65 Personal Menu Password
Range: Function:
200 N/
A*
[0 - 999 N/A] Define the password for access to the My Personal Menu via the [Quick
Menu] key. If par.0-66
Access to Personal Menu w/o Password is set to
Full access
[0], this parameter will be ignored.
0-66 Access to Personal Menu w/o Password
Option: Function:
[0] * Full access Disables password defined in par.0-65
Personal Menu Password.
[1] Read only Prevents unauthorized editing of My Personal Menu parameters.
[2] No access Prevents unauthorized viewing and editing of My Personal Menu pa-
rameters.
If par.0-61
Access to Main Menu w/o Password is set to
Full access
[0], this parameter will be ignored.
Clock Settings, 0-7*
Set the time and date of the internal clock. The internal clock can be used for e.g. Timed Actions, energy log,
Trend Analysis, date/time stamps on alarms, Logged data and Preventive Maintenance.
It is possible to program the clock for Daylight Saving Time / summertime, weekly working days/non-working
days including 20 exceptions (holidays etc.). Although the clock settings can be set via the keypad, they can also
be set along with timed actions and preventative maintenance functions using the Trane Drive Utility software
tool.
Note
The frequency converter has no back up of the clock function and the set date/time will reset to default
(2000-01-01 00:00) after a power down unless a Real Time Clock module with back up is installed. If no module
with back up is installed, it is recommended the clock function is only used if the frequency converter is inte-
grated into the BMS using serial communications, with the BMS maintaining synchronization of control
equipment clock times. In par.0-79
Clock Fault it is possible to program for a Warning in case clock has not been
set properly, e.g. after a power down.
Note
If mounting an Analog I/O MCB 109 option card, a battery back-up of the date and time is included.
0-70 Date and Time
Range: Function:
0 N/A* [0 - 0 N/A] Sets the date and time of the internal clock. The format to be used is set
in par.0-71
Date Format and par.0-72 Time Format.
0-71 Date Format
Option: Function:
Sets the date format to be used in the keypad.
[0] * YYYY-MM-DD
[1] * DD-MM-YYYY
[2] MM/DD/YYYY
0-72 Time Format
Option: Function:
Sets the time format to be used in the keypad.
[0] * 24 h
[1] 12 h
Parameter Description
TR200 Programming Guide 55