It is not possible to reset the Energy Savings counter, but the counter can be stopped any time by setting par.
23-80
Power Reference Factor to 0.
Parameter overview:
Parameter for settings
Parameters for readout
Rated Motor Power par.1-20 Motor Power
[kW]
Energy Savings par.23-83 Energy Savings
Power Reference Factor in
%
par.23-80 Power Refer-
ence Factor
Actual Power par.16-10 Power [kW],
par.16-11
Power [hp]
Energy Cost per kWh par.23-81 Energy Cost Cost Savings par.23-84 Cost Savings
Investment par.23-82 Investment
23-80 Power Reference Factor
Range: Function:
100 %* [0 - 100 %] Set the percentage of the rated motor size (set in par.1-20
Motor Power
[kW] or par.1-21 Motor Power [HP]) which is supposed to represent the
average power yielded at the time running with fixed speed (before up-
grade with variable speed control).
Must be set to a value different from zero to start counting.
23-81 Energy Cost
Range: Function:
1.00 N/
A*
[0.00 - 999999.99 N/A] Set the actual cost for a kWh in local currency. If the energy cost is
changed later on it will impact the calculation for the entire period!
23-82 Investment
Range: Function:
0 N/A* [0 - 999999999 N/A] Set the value of the investment spent on upgrading the plant with speed
control, in same currency as used in par.23-81
Energy Cost.
23-83 Energy Savings
Range: Function:
0 kWh* [0 - 0 kWh] This parameter allows a readout of the accumulated difference between
the reference power and the actual output power.
If motor size set in Hp (par.1-21
Motor Power [HP]), the equivalent kW
value will be used for the Energy Savings.
23-84 Cost Savings
Range: Function:
0 N/A* [0 - 2147483647 N/A] This parameter allows a readout of the calculation based on the above
equation (in local currency).
Parameter Description
TR200 Programming Guide 235