Chapter 11 Troubleshooting
210 BMTW-SVN01F-EN
Incorrect UCM addresses
Incompatible hardware or software versions of the UCM and/or of
Tracer Summit
Wrong or defective UCM communication card at the BCU
BCU site configuration not programmed correctly
Communication Failures that Occur After Initial
Installation
Failures that occur after successful communication following initial
installation can generally be traced to:
Wiring problems, i.e., shorts or opens that develop from wire that is
damaged from either being pulled too tightly across sharp objects or
from building vibration
Communication failures caused by nearby strong sources of
EMI/RFI interference that have been added since original wiring
installation
UCM addresses reset incorrectly after UCMs have been serviced or
replaced
AC-power disturbances (lightning, welding, etc.) that enter the UCM
communication link wiring and are strong enough to damage the
UCM communication card and/or connected UCMs
Failures of a UCM communication card and/or BCU logic board
Programming changes at the Tracer Summit PC Workstation that
alter the site configurations or UCM objects
BCU Panel Mismatch Error
The panel mismatch error is a result of active panel checking. Active
panel checking is a process by which the PC Workstation reads the type
of BCU that is connected for a given address. If the BCU hardware does
not match the BCU as defined in the Site Configuration editor, active
panel checking will discover the error. The Panel Mismatch error mes-
sage (Figure 94 on page 211) will explain the mismatch, and the Site Con-
figuration editor will be launched to allow you to resolve the error.