Amy ClarkJul 27, 2025
What causes a Trane Tracer Summit BCU panel mismatch error, and how can I resolve it?
- MMichael AtkinsJul 28, 2025
A Trane Control Systems BCU panel mismatch error can occur due to active panel checking. To resolve this, verify that the device ID of the panel you are attempting to download matches the Site Configuration address for that panel. Also, check if the panel type in the Site Configuration editor matches the panel that appears in the Panel Mismatch error message. If the Site Configuration setup for the panel matches the BCU hardware, but you still get a panel mismatch error, properly seat or change the failed hardware.