Chapter 6 UCMs supported by Tracer Summit systems
70 BMTX-SVN01C-EN
PCM: Programmable control module
Programmable control modules (PCMs) allow Tracer Summit to monitor
and control HVAC equipment such as air handlers, chillers, pumps, and
generic loads. You can also use PCMs to add generic analog and binary
inputs and outputs to Tracer Summit.
You can connect PCMs to any isolated Comm3 UCM communication link
on TB2. The link provides a serial communication interface between the
BCU and each PCM in the system. For specific information about the
number of PCMs allowed per BCU and per communication link, refer to
Table 5 on page 33.
Wiring requirements
To establish wiring connections between the UCM and the BMTX BCU,
refer to the specifications on wire type, topology, and wire procedures in “”
on page 34.
Device addressing
Each UCM must have a unique address on each link. On the PCM, the
address is set with the S2 address DIP switches. For PCM DIP switch set-
tings, refer to Table 16.
Table 16. PCM address settings
UCM
address
PCM DIP switch settings
S2-1 S2-2 S2-3 S2-4 S2-5 S2-6 S2-7 S2-8
1 OFF on on on on on OFF OFF
2 on OFF on on on on OFF OFF
3 OFFOFFononononOFFOFF
4 on on OFF on on on OFF OFF
5 OFF on OFF on on on OFF OFF
6 onOFFOFFon on onOFFOFF
7 OFF OFF OFF on on on OFF OFF
8 onononOFFononOFFOFF
9 OFF on on OFF on on OFF OFF
10 on OFF on OFF on on OFF OFF
11 OFF OFF on OFF on on OFF OFF
12 on on OFF OFF on on OFF OFF
13 OFF on OFF OFF on on OFF OFF
14 on OFF OFF OFF on on OFF OFF
15 OFF OFF OFF OFF on on OFF OFF
16 on on on on OFF on OFF OFF
17 OFFonononOFFonOFFOFF
18 on OFF on on OFF on OFF OFF