EasyManua.ls Logo

Trillium FLOWAY - Troubleshooting

Trillium FLOWAY
74 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
55 | IM-112 DECEMBER 2019
Vertical Turbine Pumps
2001299 - VTP- IOM
55 | IM-112 DECEMBER 2019
Vertical Turbine Pumps
2001299 - VTP- IOM
55 | IM-112 DECEMBER 2019
Vertical Turbine Pumps
2001299 - VTP- IOM
Vertical Turbine Pumps
Troubleshooting
Document Name: 2001299-VTP-IOM-EN Page 55 of 67
Revision 3 Copyright © 2014, Weir Floway, Inc. All Rights Reserved. Issue Date: December 12, 2014
10 Troubleshooting
Refer to Table 10-1 for troubleshooting instructions.
Condition Probable Cause Remedy
Pump not running. 1 Motor overload protection contacts open.
a Incorrect control box.
b Incorrect connections.
c Faulty overloads.
d Low Voltage.
e Ambient temperature of control box or
starter too high.
6 Blown fuse, broken or loose electric
connections.
7 Defective Motor.
8 Faulty control equipment.
9 Faulty switch.
10Pump binding.
1 Do the following:
a Check nameplate for HP and
voltage.
b Check wiring diagram furnished with
starter.
c Replace.
d Check voltage at pump side of
control box.
e Use ambient compensated relays.
6 Check fuses, relays or heater elements
for correct size and all electrical
connection.
7 Repair or replace.
8 Check all circuits and repair.
9 Repair or replace.
10Pull master switch, rotate pump by hand
to check. Check impeller adjustment or
disassemble the unit to determine the
cause.
Pump is running but
no fluid delivered.
1 Line check valve backward.
2 Line check valve stuck.
3 Unit running backwards.
4 Lift too high for pump.
5 Pump not submerged.
6 Excessive amounts of air or gas.
7 Intake strainer or impeller plugged, or pump
in mud or sand.
8 Impeller(s) loose on shaft.
1 Reverse check valve.
2 Free the valve.
3 Refer to
“Hollow Shaft Driver Installation”
on page 24, step 12.
4 Check with performance curve.
5 Lower pump if possible or add fluid to
system.
6 Correct conditions.
7 Start & stop pump several times or use
line pressure if available to back flush.
Pull pump and clean.
8 Pull unit and repair.
Reduced capacity. 1 Bypass open.
2 Lift too high for pump.
3 Motor not coming up to speed.
4 Strainer or impellers partly plugged.
5 Scaled or corroded discharge pipe or leaks
anywhere in system.
6 Excessive amounts of air or gas.
7 Excess wear due to abrasives.
8 Impellers not properly adjusted.
9 Impeller(s) loose on shaft.
1 Check bypass valving.
2 Check performance curve.
3 Check voltage while unit is running.
4 Start & stop pump several times or use
line pressure if available to back flush.
Pull pump and clean.
5 Replace pipe or repair leaks.
6 Suitable conditions.
7 Replace worn parts.
8 Refer to
“Impeller Adjustment - General”
on page 29.
9 Pull the unit and repair.
Table 10-1: Troubleshooting Chart

Table of Contents

Related product manuals