F3200 Operator's Manual Document No: LT0119
Network Systems
Page 11-20 29 July 2002 Issue 2.04
11.10.4 NETWORK ZONE ISOLATE OR DE-ISOLATE
To isolate or de-isolate a zone or range of zones on a network panel. If the network
zone(s) entered are on the local panel, then the command is implemented locally as if
the command had not used the network numbering format.
11.10.4.1 Operator Sequence - Single Network Zone
From the base display, press:
To isolate or de-isolate network zone n n n n n.
The LCD will display the selected network zone, plus the options to isolate or de-isolate
it. The status of the zone is retrieved from across the network. There may be a small
delay before this is displayed.
The display will also show options 1:Isolate and 2:De-isolate.
Select the desired option.
The LCD will display the network zone with a message saying "Sending Command".
After a brief period the message should change to "Command Accepted". Refer to
Section 11.7 for more detail on these and other possible LCD display messages.