Document No: LT0119 F3200 Operator's Manual
Operating Instructions - Zone Functions
Issue 2.04 29 July 2002 Page 7-3
OPERATING SEQUENCE (CONTINUED)
To apply a zone alarm test or zone fault test to a continuous range of zones, from the
base display press:
OR
to apply the test to the range of zones nn to mm inclusive.
- The relevant test signal is applied to the circuits.
- Once a circuit has gone into the required test state, the relevant status
LED and buzzer are turned on if that zone is not isolated and is mapped
to the MAF. For alarm test, FFCIF mode will be entered if the zone is
mapped to the MAF and the alarm must then be acknowledged.
When the zone status is displayed, the message:
"Test-Fault. Press ACK to stop" or
"Test-Alarm. Press ACK to stop"
will be shown. Pressing the "ACK" key stops the test at any point but
does not reset the zone. Pressing "RESET" followed by "ACK" will stop
the test and reset the zone.
- If the circuit does not enter the correct state in response to the test signal
then the buzzer sounds its "TEST FAIL" cadence and the LCD displays a
test fail message. Resetting the zone will terminate the test.
7.1.3 ABORT ZONE TEST
Press the "ACK" key at any time to stop the ZONE TEST function for the currently
displayed zone. This will NOT reset the zone.
Press the "RESET" key followed by "ACK" to stop the zone test and reset the circuit of
the displayed zone. It is recommended to always reset a zone at the completion of a
zone test.
A zone range reset command will terminate the zone test on each zone being reset (but
will leave zone tests running on any zones not being reset).