F3200 Operator's Manual Document No: LT0119
Operating Instructions - Zone Functions
Page 7-4 29 July 2002 Issue 2.04
7.1.4 NOTES
(a) An Alarm detected on the zone under test when one is not expected (eg
during the FAULT test) is processed as a real alarm. Similarly a fault
during the ALARM test is processed as a real fault. (After the appropriate
first condition tone on the buzzer is silenced, the second condition tone
occurs).
(b) All alarm processing delays (AVF sequences, etc) are still active so the
alarm response time will depend on the circuit type and the programmed
delays for each circuit.
(c) An AVF delay sequence initiated by a zone alarm test continues if the
zone test is aborted by the "ACK" key before the test has passed (i.e.
before the zone goes into alarm). That is, an alarm re-test of the same
zone within 150 sec will give an instant alarm.
(d) A zone alarm or fault test will be automatically terminated 5 to 6 minutes
after starting.
(e) Alarms or faults on any zones other than those under test are processed
as they normally would be and do not terminate the test.
(f) It is not possible to start a zone test if the zone is already in test or Auto-
Reset mode, or if the circuit is disabled.