Document No: LT0119 F3200 Operator's Manual
Operating Instructions - Zone Functions
Issue 2.04 29 July 2002 Page 7-13
OPERATING SEQUENCE - ZONE STATUS (CONTINUED)
fault - the zone is in fault.
isolated - the zone is isolated.
deisolated - (or deiso) the zone is de-isolated.
FIP MCP - the FIP MCP maps to this zone.
Status Only - the zone is a status only type.
disabled - the circuit is disabled but the zone may still have the FIP MCP
mapped to it. Thus it can still produce alarms and faults, and
signal the Brigade but alarms and faults will never be produced by
the detector circuit on the AZC module.
If the zone is currently in zone alarm test, zone fault test, Auto-Reset mode or being
reset, then the zone name on the top line of the display will be replaced by one of the
following messages.
"resetting" - If the zone is currently being reset.
"Test-alarm. Press ACK to stop" - If a zone alarm test is operating.
"Test-alarm failed. Press ACK" - If a zone alarm test has failed.
"Test-fault. Press ACK to stop" - If a zone fault test is operating.
"Test-fault failed. Press ACK" - If a zone fault test has failed.
"Auto-Reset Mode Bn" - If the zone is in Auto-Reset mode. Bn is one of
B1, B2, B3, B4 or B5 depending on the current
voltage applied to the circuit input.