F3200 Operator's Manual Document No: LT0119
Operating Instructions - Zone Functions
Page 7-14 29 July 2002 Issue 2.04
7.5.3 OPERATING SEQUENCE - ZONE SEARCHES
The zone search functions allow an operator to query the FIP for zones meeting
specified status criteria, e.g. in alarm.
To start a search from the base display, press:
Then select the option required. Note Status Only zones do not appear in the alarms,
faults or isolate recalls. Valid options are:
"1" all off normal Searches for any zones in alarm, fault or isolated, or in
zone test or Auto-Reset mode.
"2" alarms - Searches for any zones in alarm, whether or not they
are isolated or mapped to MAF.
"3" faults - Searches for any zones in fault, whether or not they
are isolated or mapped to MAF.
"4" testing - Searches for any zone in zone alarm test, zone fault
test or Auto-Reset mode (independent of zone type
and mapping).
"5" isolated - Searches for any zones that are isolated or in Auto-
Reset mode, whether or not they are mapped to the
MAF.
"6" status - Prompts for a zone number and displays the status of
that zone as described in Section 7.5.2.
When an option has been selected, the FIP searches for a zone starting from Zone 1 up
to the programmed maximum zone that meets the specified criteria.
Once a zone is found that meets the specified criteria, the LCD display reverts to a zone
status display for that zone. When the "NEXT" or "PREV" key is pressed, the search
continues for the next or previous zone respectively, that meets the original search
criteria.
If no zones matching the criteria are found, the LCD briefly displays a message saying
so, and reverts to the base display.