4 - 36 Configuration Issue 13 February 2001
STC: The configuration of this field enables or disables Slope Thermal
Compensation feature. Use the <+> or <-> key to toggle between enable
or disable. Press <ENTER> to save the change.
LOW TEMP: The configuration of this field sets the temperature at
which the plant voltage will have raised 0.1 volts x the number of cells.
Valid range is 23° to 68° F or -5° to 20° C. Use the <+> or <-> key to
adjust the temperature to the desired level. Press <ENTER> to save the
change.
NOM TEMP: The configuration of this field sets the temperature at
which the plant voltage is set to its nominal value. Compensation begins
at temperatures above or below this point. Valid range is 59° to 86° F or
15° to 30° C. Use the <+> or <-> key to adjust the temperature to the
desired level. Press <ENTER> to save the change.
Note: It is critical that the NOM TEMP value be adjusted from its
default value to 25°C or 77°F for all known types of batteries before
STC is enabled. An undercharge condition of the plant batteries will
result if STC is configured to reduce plant voltage starting at the
15°C or 59°F default values for this field.
UPPER TEMP: The configuration of this field sets the temperature at
which the plant voltage will have decreased 0.1 volts x the number of
cells. Use the <+> or <-> key to adjust the temperature to the desired
level. Press <ENTER> to save the change.
RAISE VOLTS: The configuration of this field enables or disables the
increase in plant voltage due to decrease in battery temperature. Use the
<+> or <-> key to toggle between enable or disable. Press <ENTER> to
save the change.
STEP COMPENSATION: The configuration of this field sets the
temperature at which the plant voltage will be further decreased by a
factor determined by multiplying the number of cells in the battery
string by 0.17. For example in a 24 cell plant, battery voltage will be
decreased by 4.08 volts (24 x 0.17 = 4.08).
Battery Control
Menu
This menu selection applies only to controllers used with serial interface
rectifiers, connected with bus wiring through the L-36 Rectifier
Interface Module and L-23, BJC3 Rectifier Interface Board. From the
BATTERY MANAGEMENT menu select BAT CNTRL to bring up
the BATTERY CONTROL menu. This menu allows you to configure
the various parameters for two optional low voltage disconnect
contactors.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tyco Galaxy SC Controller and is the answer not in the manual?

Tyco Galaxy SC Controller Specifications

General IconGeneral
BrandTyco
ModelGalaxy SC Controller
CategoryController
LanguageEnglish

Related product manuals