Tyco Electronics Galaxy SC Controller J85501F-1
6 - 4 Operation Issue 13 February 2001
Change Plant
Voltage (Serial Bus
Rectifiers Only)
To make adjustment to the plant voltage, first press the <MENU> key
to bring up the MAIN menu; move the cursor to the CONFIG field;
press <ENTER> to bring up the Configuration menu; move the cursor
to RECT MNGR to bring up the Rectifier Management menu; move the
cursor to RECT OPER to bring up the Rectifier Operations menu; and
move the cursor to PLANT V (FLOAT or BOOST) as applicable. Use
the <UP> <DOWN> arrow keys to change to the desired value. Press
<ENTER> to save the change.
Clear Latched
Events
Some events in the system stay active after the fault has cleared and can
only be cleared by the users. These are known as latched events. In
order to retire them, press the <MENU> key to bring up the MAIN
menu, move the cursor to the MAINT OPER field, press <ENTER>,
then move to the CLR EVENT field and press <ENTER>. The system
will respond with a CLEARING USER CLEARABLE EVENTS
confirmation message.
Disable/Enable
Efficiency
Disabling the efficiency feature will start all rectifiers. It may be done
by toggling the hardware switch at SW204-1 on the BJH pack or in
software. From the Front Panel, press the <MENU> key to bring up the
MAIN menu; move the cursor to the CONFIG field; press <ENTER> to
bring up the Configuration menu; move the cursor to RECT MNGR to
bring up the Rectifier Management menu; move the cursor to RECT
CTR to bring up the Rectifier Control menu; move the cursor to the
EFFICIENCY: field. Use the <UP> <DOWN> arrow keys to toggle to
the desired value. Press <ENTER> to save the change.
Display Alarm
Data
The steps to view the alarm data on the system equipped with Intelligent
Controller are the same as the system equipped with the Basic Controller
option. Please refer to Display Alarm data for the Basic Controller
above.
Display Warning
Data
The steps to view the warning data on the system equipped with
Intelligent Controller are the same as the system equipped with the Basic
Controller option. Please refer to Display Alarm data for the Basic
Controller above.
Performing
Rectifier Restart
To perform the rectifier restart from the front panel. Press <MENU> key
to bring up the MAIN menu, move the cursor to the MAINT OPER
field, press <ENTER>, then move to the RECT RST field and press

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tyco Galaxy SC Controller and is the answer not in the manual?

Tyco Galaxy SC Controller Specifications

General IconGeneral
BrandTyco
ModelGalaxy SC Controller
CategoryController
LanguageEnglish

Related product manuals