Tyco Electronics Galaxy SC Controller J85501F-1
Issue 13 February 2001 Operation 6 - 11
The backup and restore feature allows the user to back up the system
configuration to disk, in a series of T1.317 commands in the ASCII
format. The user may edit the file and before restoring it.
Boost/Float Mode
Control
EasyView path: Main Control Plant Mode Boost must be enabled
in both hardware and software in order to initiate Boost. The matrix
found under Main Configure Plant Hardware & Software
Config will define the configured state for Boost. Plant rectifiers must
be able to accept the Boost signal and should have their Boost
adjustment potentiometers set to the desired Boost voltage in order to
utilize this feature. Also note that the Boost HV and HFV levels found
under Main Configure Alarms Thresholds must be higher than
the desired Boost voltage level in order to avoid nuisance alarms and
shutdowns.
Changing Plant
Voltage (Serial Bus
Rectifiers Only)
Easy View Path: Main Rectifier Rectifier Manager. This path
allows adjustment to the plant voltage in the Float and Boost modes. The
rectifiers current limits and HVSD set points are also configured here.
Clear Latched
Events
EasyView path: Main Control Clear Latched Events. Some events
that occur remain on the active Alarm or Warning display after they
have cleared to alert the user to their occurrence. These are known as
User-Clearable or Latched events. This EasyView path can be used
to clear these events after they have been investigated by the user.
Diagnostics EasyView path: Main Status Diagnostics All / Monitoring /
Plant / Rectifiers. If an alarm is active, the user can select this path to
obtain some help on what the trouble could be. Plant here refers to
system diagnostics while Monitoring refers to those associated with
Remote Peripheral Monitors.
Disable/Enable
Efficiency
Disabling the efficiency feature will start all rectifiers. It may be done
toggling the hardware switch at SW204-1 on the BJH pack or in
software. In Easy View follow the path: Main Configure DC Plt
(Hardware & Software Configured).
Display Alarms
and Warnings
Active Alarms and Warnings are always shown in their appropriate
fields on the Main display. Galaxy SC and EasyView update every few
seconds to keep this information current as long as the current session is
active.

Table of Contents