Tyco Electronics Galaxy SC Controller J85501F-1
6 - 12 Operation Issue 13 February 2001
Display Alarm Test EasyView path: Status → Alarm Test. Information on the success or
failure of the last Alarm Test that was performed is provided.
Display Battery
Sections
EasyView path: Status → Battery Sections. Displays the present values
of the reserve, voltage, charge current, discharge current, temperature
and fuse state that may have been optionally linked to Remote
Peripheral Monitor channels.
Display DC Plant EasyView path: Status → DC Plant. Displays the present values of the
plant voltage, current, total rectifier drain, ambient temperature,
temperature probe present, reserve time, battery thermal integrity,
transfer times and universal battery temperature. Many of these items
are options within the plant and must be installed and enabled.
Display
Distribution AC
EasyView path: Status → Distribution AC. Displays the values of ac
phase voltages and currents that may have been optionally linked to
Remote Peripheral Monitor channels.
Display
Distribution DC
EasyView path: Status → Distribution DC. Displays the state of a
distribution fuse alarm that may have been optionally linked to a Remote
Peripheral Monitor channel.
Display Record
Only Alarms
EasyView path: Main → Status → Record Only Alarms. Alarms
designated as “Record Only” will not appear on the Main Menu display
of EasyView or on the Front Panel interface of Galaxy SC.
Display Rectifier EasyView path: Status → Rectifier → Rectifier. Displays the rectifiers
output current, On/Off state, output current, state of it's DC breaker and
the of state of the ac circuit breaker that may have been optionally linked
to a Remote Peripheral Monitor channel.
Display Rectifier
Bays
EasyView path: Status → Rectifier → Rectifier Bays. Displays the state
of an ac circuit breaker and temperature value for a rectifier bay that may
have been optionally linked to a Remote Peripheral Monitor channel.
History A wealth of data is available under History. The EasyView path to this
data is Main → History → Alarm Cut-Off / Alarm Test / All / Battery
On Discharge / Battery Reserve / Boost / Control Relay / Call Out