Tyco Electronics Galaxy SC Controller J85501F-1
Issue 13 February 2001 Operation 6 - 13
Manager / Log In / Periodic Status Call Out / Plant / Rectifiers / System
/ User Defined.
Measurements Plant voltage and load values are constantly displayed and updated on
the status bar at the bottom of the EasyView Main Menu. Rectifier
current measurements are obtained through the path: Main Status
Rectifier and Remote Peripheral Module measurements are obtained
through Main Status Monitored Channels Shunt Channels /
Temperature Channels / Voltage Channels.
Rectifier Control EasyView path: Main Control Rectifiers/1-8/9-16/17-24. This
menu shows the present state of the rectifiers and allow the user to
toggle them ON / OFF individually. Rectifiers in the on state can be
turned off, if the hardware switch SW203-8 on the BJH pack and
software switch at Main Configure Hardware & Software
Configured are enabled. Rectifiers turned off via the terminal or by the
efficiency can be turned on if hardware switch SW203-7 on the BJH
pack and the applicable software switch are enabled.
Rectifier Removal
(Serial Bus
Rectifiers Only)
EasyView path: Main Configure Rectifier Rectifier. Serial
Rectifiers are automatically recognized by the system when plugged in
and the RID is configured at the rectifier. The system remains
configured even if the rectifier should be removed or sent in for repair.
Changing the rectifier configuration by selecting the VACANT
button on the desired rectifiers configuration screen, after the rectifier
is disconnected, will remove the alarm from the system.
Rectifier Restart EasyView path: Main Control Rectifier Restart. This path will be
useful when completing high voltage shutdown testing of plant
rectifiers. If the controller has shut down for the second time, and locked
out the rectifier being tested, the restart timer will be cleared and testing
can resume immediately without waiting for its 5 minute time-out to
clear.
Statistics Like History, a wealth of data is also available under Statistics. The
EasyView path for Basic Statistics is: Main Reports Statistics
Basic DC Current / DC Voltage / Rectifiers / Total Rectifier Drain /
Universal Battery Temp / User Defined Objects. Other Statistics
available include: Main Reports Statistics Battery on Discharge
/ Busy Hour / Derived Channel / Remote Peripheral Monitor / Trend.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tyco Galaxy SC Controller and is the answer not in the manual?

Tyco Galaxy SC Controller Specifications

General IconGeneral
BrandTyco
ModelGalaxy SC Controller
CategoryController
LanguageEnglish

Related product manuals