Tyco Electronics Galaxy SC Controller J85501F-1
Issue 13 February 2001 T1.317 Interface Appendix A - 11
error occurred while processing the command then a line preceded by
the ! (exclamation) character will give an error code and short
description of the error.
ALA Report active alarms
Syntax:ALA [objpath]
This command searches the objects that objpath leads to, and all objects
linked to these objects, for active alarms. If objpath is omitted, all active alarms
are reported. Each line in the report has the following format:
event_path,date,time,severity,description
The following examples will report all the active alarms in the system and just
the DC plant active alarms:
ALA
ALA DC1
ALI Report aliases
Syntax: ALI
ALI alias<,alias>*
If alias is omitted, all aliases in the system are reported. The system defined
aliases are reported first followed by the user defined aliases. The system de-
fined aliases are reported with the alias name in uppercase. The user defined
aliases are reported with the alias name in lowercase. If alias is included in the
command line, only the aliases that appear in the command will be reported.
Each alias is reported using the following format:
alias=command_line
ATT Report the object attributes
Syntax:ATT objpath
This command reports just the attribute mnemonics of objects that objpath
leads to. Attributes are reported one per line. For example, ATT DC1 will list all
the attributes mnemonics of the DC1 object.
CON Report the settings of configuration and operation attributes
Syntax:CON objpath
This command reports the values of attributes that can be changed by the CHA
command or the OPE command. It is useful for limiting a report to only those
attributes that are settable.
DIA Report diagnostic information
Syntax:DIA [objpath]
This command reports diagnostic information for the entire system or just the
objects that objpath leads to. This command is useful for additional information
on active alarms or warnings in the system. The following example will retrieve
all diagnostics information and just the DC plant diagnostics information:
DIA
DIA DC1
HELP Report the customer service 800 number
Syntax: HELP
This command returns: 1-800-THE-1PWR.
HIS Report event history information
Syntax: HIS objpath<,hisoption=value>*
HIS [hisoption=value<,hisoption=value>*]
where hisoption and value are defined as follows:
hisoption value
g for group 0:no 1:yes (default:0)