Uponor Smatrix Base T-149
Alarm symbols
The figure shows all possible symbols and characters that can be
shown on the display:
B
A
D
C
CD0000150
Item Icon Description
A Alarm mode
B Faulty indoor temperature sensor
Faulty floor temperature sensor
Faulty remote temperature sensor
Faulty outdoor temperature sensor
C Relative humidity limit reached (high limit)
This symbol is only shown if cooling is active, and if
RH control is be activated in Uponor Smatrix PULSE
app (requires communication module).
D Communication fault indicator
Alarm icon is displayed
An error has occured
-
Go to the alarm list for more information
The display is off
The cable is not connected or a wire is damaged
-
Check the wiring
-
Connect the thermostat directly to the room controller with
a short bus connection to verify thermostat functionality.
If the thermostat functions correctly check the existing
wiring (cable and connections) before replacing the wiring,
otherwise replace the thermostat.
Communication fault icon is displayed in the alarm
list
The cable is not connected or a wire is damaged
-
Check the wiring
-
Connect the thermostat directly to the room controller with
a short bus connection to verify thermostat functionality.
If the thermostat functions correctly check the existing
wiring (cable and connections) before replacing the wiring,
otherwise replace the thermostat.
The thermostat is faulty
-
Force the thermostat to transmit by changing the
temperature setpoint
-
Replace thermostat
Relative humidity icon is displayed in the alarm list
Note
RH control is activated in the Uponor Smatrix PULSE
app (requires communication module).
The relative humidity limit is reached
-
Lower the humidity level by increasing the ventilation or
activating a dehumidifier
Floor temperature sensor icon is displayed in the
alarm list
Faulty temperature sensor
-
Check the connection of the floor sensor
-
Disconnect the temperature sensor and check it with an
ohmmeter. Make sure the value aligns with the
temperatuer sensor diagram, see External temperature
sensor resistance diagram, Page 87
Incorrect thermostat control mode, or temperature sensor not
connected
-
Select correct thermostat control mode (settings menu 4)
Outdoor temperature sensor icon is displayed in
the alarm list
Faulty temperature sensor
-
Check the connection of the outdoor sensor
-
Disconnect the temperature sensor and check it with an
ohmmeter. Make sure the value aligns with the
temperatuer sensor diagram, see External temperature
sensor resistance diagram, Page 87
Incorrect thermostat control mode, or temperature sensor not
connected
-
Select correct thermostat control mode (settings menu 4)
Indoor temperature sensor icon is displayed in the
alarm list
Faulty temperature sensor
-
Contact the installer or replace the thermostat
Remote temperature sensor icon is displayed in the
alarm list
Faulty temperature sensor
-
Check the connection of the remote sensor
-
Disconnect the remote temperature sensor and check it
with an ohmmeter. Make sure the value aligns with the
temperatuer sensor diagram, see External temperature
sensor resistance diagram, Page 87
Incorrect thermostat control mode, or temperature sensor not
connected
-
Select correct thermostat control mode (settings menu 4)
86
|
Uponor Smatrix Base PULSE
|
Installation and operation manual

Table of Contents

Other manuals for Uponor Smatrix Base PULSE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Uponor Smatrix Base PULSE and is the answer not in the manual?

Uponor Smatrix Base PULSE Specifications

General IconGeneral
BrandUponor
ModelSmatrix Base PULSE
CategoryController
LanguageEnglish

Related product manuals