Table 41: The minimum resistance and the brake power, mains voltage
380-500 V
Frame The minimum brake
resistance [Ω]
Brake power* @845 VDC
[kW]
MR4 63.0 11.3
MR5 41.0 17.0
MR6 21.0 34.0
MR7 14.0 51.0
MR8 6.5 109.9
MR9 3.3 216.4
* = When you use recommended resistor types.
Table 42: The minimum resistance and the brake power, mains voltage
525-600 V
Frame The minimum brake
resistance [Ω]
Brake power* @1014 VDC
[kW]
MR5 100 7.5
MR6 30 22.4
MR7 18 44.8
MR8 9 93.3
MR9 7 145
* = When you use recommended resistor types.
Table 43: The minimum resistance and the brake power, mains voltage
525-690 V
Frame The minimum brake
resistance [Ω]
Brake power* @1166 VDC
[kW]
MR6 30 30
MR7 18 55
MR8 9 110
MR9 7 193
* = When you use recommended resistor types.
TECHNICAL DATA, VACON® 100 VACON · 127