Fig. 35: The principal connection diagram
A. The control panel
B. The control unit
C. The power unit
Use cables with a minimum heat resistance of +70 °C (158 °F). In the selection of the cables
and the fuses, refer to the nominal output current of the drive. You can find the nominal
output current on the nameplate.
Table 15: The selection of the correct cable
Cable type EMC requirements
1
st
environment 2
nd
environment
Category C2 Category C3 Category C4
The mains cable 1 1 1
The motor cable 3 * 2 2
The control cable 4 4 4
POWER CABLING VACON · 57
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM