9.1.4 MAINS VOLTAGE 525-690 V
Table 48: The power ratings of Vacon
®
100 FLOW in mains voltage 525-690 V, 50-60 Hz, 3~
Frame Drive type Loadability Motor shaft power
Continuous
current I
L
[A]
Input
current I
in
[A]
10%
overload
current [A]
Max
continuous
current I
S
2s
600 V 690 V
10%
overload
40°C [Hp]
10%
overload
40°C [kW]
MR6 0007 7.5 6.8 8.3 11.0 5.0 5.5
0010 10.0 9.0 11.0 15.0 7.5 7.5
0013 13.5 11.6 14.9 20.0 10.0 11.0
0018 18.0 15.2 19.8 27.0 15.0 15.0
0022 22.0 19.8 24.2 36.0 20.0 18.5
0027 27.0 23.1 29.7 44.0 25.0 22.0
0034 34.0 27.0 37.4 54.0 30.0 30.0
MR7 0041 41.0 38.4 45.1 68.0 40.0 37.0
0052 52.0 44.9 57.2 82.0 50.0 45.0
0062 62.0 53.2 68.2 104.0 60.0 55.0
MR8 0080 80.0 72.0 88.0 124.0 75.0 75.0
0100 100.0 89.0 110.0 160.0 100.0 90.0
0125 125.0 104.0 137.5 200.0 125.0 110.0
MR9 0144 144.0 140.0 158.4 250.0 150.0 132.0
0170 170.0 155.0 187.0 288.0 150.0 160.0
0208 208.0 177.0 228.8 340.0 200.0 200.0
9.1.5 OVERLOAD CAPABILITY
The low overload means that if 110% of the continuous current (I
L
) is required for 1 minute
every 10 minutes, the remaining 9 minutes must be approximately 98% of I
L
or less. This is to
make sure that the output current is not more than I
L
during the duty cycle.
TECHNICAL DATA, VACON® 100 FLOW VACON · 137
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM