EasyManua.ls Logo

Vacon 100 - The EMC Jumper in MR7

Vacon 100
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 After the change, write "The EMC level was
changed" and the date on the "product modified"
label. If the label is not attached at this time, attach
it on the drive near the name plate.
Product modified
Date:
Date:
Date:
7.6.2 THE EMC JUMPER IN MR7
Change the EMC protection of the AC drive to level C4.
HOW TO FIND THE EMC JUMPERS, 200-500 V
1 Open the cover of the AC drive.
2 Find the EMC box. To get access to the EMC
jumper, remove the cover of the EMC box.
3 Remove the EMC jumper. Attach the cover of the
EMC box again.
VACON · 112 COMMISSIONING AND ADDITIONAL INSTRUCTIONS