9 TECHNICAL DATA, VACON
®
100 FLOW
9.1 AC DRIVE POWER RATINGS
9.1.1 MAINS VOLTAGE 208-240 V
Table 45: The power ratings of Vacon
®
100 FLOW in mains voltage 208-240 V, 50-60 Hz, 3~
Frame Drive type Loadability * Motor shaft power
Continuous
current I
L
[A]
Input
current I
in
[A]
10%
overload
current [A]
Max
current I
S
2s
230 V
mains
230 V
mains
10%
overload
40°C [kW]
10%
overload
40°C [hp]
MR4 0003 3.7 3.2 4.1 5.2 0.55 0.75
0004 4.8 4.2 5.3 7.4 0.75 1.0
0007 6.6 6.0 7.3 9.6 1.1 1.5
0008 8.0 7.2 8.8 13.2 1.5 2.0
0011 11.0 9.7 12.1 16.0 2.2 3.0
0012 12.5 10.9 13.8 19.6 3.0 4.0
MR5 0018 18.0 16.1 19.8 25.0 4.0 5.0
0024 24.0 21.7 26.4 36.0 5.5 7.5
0031 31.0 27.7 34.1 46.0 7.5 10.0
MR6 0048 48.0 43.8 52.8 62.0 11.0 15.0
0062 62.0 57.0 68.2 96.0 15.0 20.0
MR7 0075 75.0 69.0 82.5 124.0 18.5 25.0
0088 88.0 82.1 96.8 150.0 22.0 30.0
0105 105.0 99.0 115.5 176.0 30.0 40.0
MR8 0140 143.0 135.1 154.0 210.0 37.0 50.0
0170 170.0 162.0 187.0 280.0 45.0 60.0
0205 208.0 200.0 225.5 340.0 55.0 75.0
MR9 0261 261.0 253.0 287.1 410.0 75.0 100.0
0310 310.0 301.0 341.0 502.0 90.0 125.0
* = See chapter 9.1.5 Overload capability.
TECHNICAL DATA, VACON® 100 FLOW VACON · 133
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM