Table 53: The standard I/O board
Standard I/O board
Terminal Signal Technical information
12 24 V aux. voltage
+24 V, ±10%, max volt. ripple < 100mVrms
max. 250 mA
Short-circuit protected
13 I/O ground
Ground for reference and controls (connected internally to
frame ground through 1 MΩ)
14 Digital input 4
Positive or negative logic
Ri = min. 5 kΩ
0-5 V = 0
15-30 V = 1
15 Digital input 5
16 Digital input 6
17 Common A for DIN1-DIN6
Digital inputs can be isolated from ground, see chapter
6.2.2.2 Isolation of digital inputs from ground.
18 Analogue signal (+output)
Analogue output channel 1, selection 0 -20 mA, load <500 Ω
Default: 0-20 mA
0-10 V
Resolution 0.1 %, accuracy ±2 %
Selection V/mA with dip-switches (see chapter 6.2.2.1 Selec-
tion of terminal functions with DIP switches)
Short-circuit protected
19 Analogue output common
30 24V auxiliary input voltage Can be used as external power backup for the control unit
A RS485
Differential receiver/transmitter
Set bus termination with dip switches (see chapter 6.2.2.1
Selection of terminal functions with DIP switches). Termination
resistance = 220 Ω
B RS485
TECHNICAL DATA ON CONTROL CONNECTIONS VACON · 153
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
11