Table 16: The cable and fuse sizes for Vacon
®
100, mains voltage 208-240 V and 380-500 V
Frame Type IL [A] Fuse
(gG/gL)
[A]
Mains, motor and
brake resistor*
cable Cu [mm
2
]
Terminal cable size
Mains cable
terminal
[mm
2
]
Grounding
terminal
[mm
2
]
MR4
0003 2—0004 2
0003 5—0004 5
3.7—4.8
3.4—4.8
6 3x1.5+1.5 1—6 solid
1—4 stranded
1-6
0006 2—0008 2
0005 5—0008 5
6.6—8.0
5.6—8.0
10 3x1.5+1.5 1—6 solid
1—4 stranded
1-6
0011 2—0012 2
0009 5—0012 5
11.0—12.5
9.6—12.0
16 3x2.5+2.5 1—6 solid
1—4 stranded
1-6
MR5
0018 2
0016 5
18.0
16.0
20 3x6+6 1—10 Cu 1-10
0024 2
0023 5
24.0
23.0
25 3x6+6 1—10 Cu 1-10
0031 2
0031 5
31.0
31.0
32 3x10+10 1—10 Cu 1-10
MR6
0038 5 38.0 40 3x10+10 2.5—50 Cu/Al 2.5-35
0048 2
0046 5
48.0
46.0
50 3x16+16 (Cu)
3x25+16 (Al)
2.5—50 Cu/Al 2.5-35
0062 2
0061 5
62.0
61.0
63 3x25+16 (Cu)
3x35+10 (Al)
2.5—50 Cu/Al 2.5-35
MR7
0075 2
0072 5
75.0
72.0
80 3x35+16 (Cu)
3x50+16 (Al)
6-70 mm
2
Cu/Al
6-70 mm
2
0088 2
0087 5
88.0
87.0
100 3x35+16 (Cu)
3x70+21 (Al)
6-70 mm
2
Cu/Al
6-70 mm
2
0105 2
0105 5
105.0 125 3x50+25 (Cu)
3x70+21 (Al)
6-70 mm
2
Cu/Al
6-70 mm
2
MR8
0140 2
0140 5
140.0 160 3x70+35 (Cu)
3x95+29 (Al)
Bolt size M8 Bolt size M8
0170 2
0170 5
170.0 200 3x95+50 (Cu)
3x150+41 (Al)
Bolt size M8 Bolt size M8
0205 2
0205 5
205.0 250 3x120+70 (Cu)
3x185+57 (Al)
Bolt size M8 Bolt size M8
MR9
0261 2
0261 5
261.0 315 3x185+95 (Cu)
2x3x120+41 (Al)
Bolt size M10 Bolt size M8
0310 2
0310 5
310.0 350 2x3x95+50 (Cu)
2x3x120+41 (Al)
Bolt size M10 Bolt size M8
VACON · 60 POWER CABLING