Table 19: The cable and fuse sizes for Vacon
®
100 in North America, mains voltage 525-690 V
Frame Type IL [A] Fuse
(Class T/J)
[A]
Mains, motor
and brake
resistor*
cable Cu
[AWG]
Terminal cable size
Mains cable
terminal [AWG]
Grounding
terminal [AWG]
MR5 (600
V)
0004 6 3.9 6 14 20-5 17-8
0006 6 6.1 10 14 20-5 17-8
0009 6 9.0 10 14 20-5 17-8
0011 6 11.0 15 14 20-5 17-8
MR6 0007 7 7.5 10 12 13-0 13-2
0010 7 10.0 15 12 13-0 13-2
0013 7 13.5 20 12 13-0 13-2
0018 6
0018 7
18.0 20 10 13-0 13-2
0022 6
0022 7
22.0 25 10 13-0 13-2
0027 6
0027 7
27.0 30 8 13-0 13-2
0034 6
0034 7
34.0 40 8 13-0 13-2
MR7 0041 6
0041 7
41.0 50 6 9-2/0 9-2/0
0052 6
0052 7
52.0 60 6 9-2/0 9-2/0
0062 6
0062 7
62.0 70 4 9-2/0 9-2/0
MR8 0080 6
0080 7
80.0 90 1/0 1 AWG-350 kcmil 1 AWG-350 kcmil
0100 6
0100 7
100.0 110 1/0 1 AWG-350 kcmil 1 AWG-350 kcmil
0125 6
0125 7
125.0 150 2/0 1 AWG-350 kcmil 1 AWG-350 kcmil
POWER CABLING VACON · 67