46 • vacon description of parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205
7
348 Torque limit, supervision function
(2.3.4.5)
0 = No supervision
1 = Low limit supervision
2 = High limit supervision
3 = Brake-off control (See chapter Error! Reference source not found. on page Error!
Bookmark not defined.)
If the calculated torque value falls below or exceeds the set limit (ID349) this function
generates a warning message via the digital output DO1 or via a relay output RO1 or RO2
depending on to which output the supervision signal (par. ID451) is connected.
349 Torque limit, supervision value
(2.3.4.6)
Set here the torque value to be supervised by parameter ID348.
350 Reference limit, supervision function
(2.3.4.7)
0 = No supervision
1 = Low limit supervision
2 = High limit supervision
If the reference value falls below or exceeds the set limit (ID351), this function generates
a warning message via the digital output DO1 or via a relay output RO1 or RO2 depending
on to which output the supervision signal (par. ID449) is connected
The supervised reference is the current active reference. It can be place A or B
reference depending on DIN6 input, or panel reference if the panel is the active control
place.
351 Reference limit, supervision value
(2.3.4.8)
The frequency value to be supervised with the parameter ID350.
354 Frequency converter temperature limit supervision
(2.3.4.11)
0 = No supervision
1 = Low limit supervision
2 = High limit supervision
If the temperature of the frequency converter unit falls below or exceeds the set limit
(ID355), this function generates a warning message via the digital output DO1 or via a
relay output RO1 or RO2 depending on to which output the supervision signal (par. ID450)
is connected.
355 Frequency converter temperature limit value
(2.3.4.12)
This temperature value is supervised by parameter ID354.

Table of Contents

Other manuals for Vacon NXP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon NXP and is the answer not in the manual?

Vacon NXP Specifications

General IconGeneral
BrandVacon
ModelNXP
CategoryMedia Converter
LanguageEnglish

Related product manuals