X5 AC Drive User’s Manual Chapter 4: Connections
DPD00089A - 30 - © 2009 Vacon Incorporated All Rights Reserved
Note: Wire type not specified by the manufacturer. Some types of wire may not fit within the constraints of the
conduit entry and bend radius inside the drive..
4.2.3 Considerations for Control Wiring
Control wiring refers to the wires connected to the control terminal strip. Select control wiring as
follows:
1. Shielded wire is recommended to prevent electrical noise interference from causing improper operation
or nuisance tripping.
2. Use only UL recognized wire.
3. Wire voltage rating must be at least 300 V for 230 Vac systems. It must be at least 600 V for 460 or
575 Vac systems.
See Table 4-3 below for a summary of control wiring specifications.
Table 4-1: X5 Power Terminal Wiring Specifications
Frame Size
Specifications
Torque Nom. Torque Max. Max. Wire Size Strip Length
Size 0 12 in-lbs 13 in-lbs 12-24 AWG 5/16” (0.3125”)
Size 1 16 in-lbs 18 in-lbs 8-18 AWG 5/16” (0.3125”)
Size 2 30 in-lbs 6-8 AWG 3/8” (0.38”)
Size 3 35 in-lbs 3 AWG
Size 4 65 in-lbs 3/0 AWG
Size 5 132 in-lbs 400 MCM
Table 4-2: User-Supplied Terminal Cross-Reference
Wire Size Manufacturer Manufacturer’s P/N Manufacturer Manufacturers P/N
3 AWG T&B 54107
2 AWG T&B 54107
1 AWG T&B 54108
1/0 AWG T&B 54152-TB Burndy YA25-L6BOX
2/0 AWG T&B 54157 Burndy YA26-L5BOX
3/0 AWG T&B 54162-TB Burndy YA27-LBOX
4/0 AWG Burndy YA28-LBOX
250 MCM Burndy YA29-LBOX
300 MCM Burndy YA30-L
350 MCM Burndy YA31-L
400 MCM Burndy YA32-L1
Table 4-3: X5 Control Wiring Specifications
X5 Size / Models Specifications
All Sizes / Models
4.4 in-lbs maximum torque
12-24 awg wire
9/32” strip length