X5 AC Drive User’s Manual Chapter 6: Using Macro Mode / Quick Start
DPD00089A - 63 - © 2009 Vacon Incorporated All Rights Reserved
6.3 Macro Mode Applications and Included Parameters
The tables below list the different applications and the Level 1 parameters included in the macro for
that application. The Factory Application macro is the core package (listed in Table 6-1); the other
macros include the Factory Application macro parameters as well as the ones listed in their
respective tables (Tables 6-2, 6-3, 6-4, 6-5, and 6-6). The macro mode applications are as follows:
Factory Application (Table 6-1)
Fan Application (Table 6-2)
Fan with PI Application (Table 6-3)
Pump Application (Table 6-4)
Pump with PI Application (Table 6-5)
Vector Application (Table 6-6)
Table 6-1: Factory Application Macro
Para. # Parameter Name Default See Page
001 Model Number Read-only 71
102 Output Freq Read-only 72
103 Output Voltage Read-only 72
104 Output Current Read-only 72
105 Drive Load Read-only 72
106 Load Torque Read-only 72
107 Drive Temp Read-only 72
111 DC Bus Voltage Read-only 72
201 Input Mode Local Only 75
202 Rev Enable Forward 75
301 Min Frequency 0.0 Hz 79
302 Max Frequency 60.0 Hz 79
303 Preset Freq 1 5.0 Hz 79
402 Accel Time 1 5.0 sec 81
403 Decel Time 1 5.0 sec 81
502 Voltage Boost 0.0% 85
610 Timed OL Select Std Ind 60s 90
700 Vmet Config Freq Out 91
705 Relay 1 Select Drv Fault 93
706 Relay 2 Select Drive Run 93