9 L&J TankWay
Varec, Inc. 115
3. Press Enter to modify the Temp Display Units parameter.
4. Press Minus or Plus to move to the appropriate Temp Display Units for this device.
5. Continue following steps 9 through 12 above to complete the Temp Display Units setup.
To Set the 2920 FTT Calibration Level
1. Follow steps 1 through 5 in the 2920 FTT unit address procedure (above).
2. In the Config Params menu, select Calibration Level.
3. Press Enter to modify the Calibration Level parameter.
4. Press Minus or Plus to move to the appropriate Calibration Level for this device.
5. Continue following steps 9 through 12 above to complete the Calibration Level setup.
To Set the 2920 FTT Control Mode
1. Follow steps 1 through 5 in the 2920 FTT unit address procedure (above).
2. In the Config Params menu, select Control.
3. Press Enter to modify the Control parameter.
4. Press Minus or Plus to move to the appropriate Control setting for this device.
5. Continue following steps 9 through 12 above to complete the Control setup.