MODBUSAppendix A — MODBUS Implementation
Varec, Inc. 165
288 Coded DO #4 Output Assignment: (Digital Outputs >
DO4 Assignment)
0 - Not Assigned
1 - Host Control
2 - Critical High Level
3 - Advisory High Level
4 - Advisory Low Level
5 - Critical Low Level
6 - Critical High Temp
7 - Advisory High Temp
8 - Advisory Low Temp
9 - Critical Low Temp
289 Integer DO1 Output on Duration (Seconds) (Digital Outputs >
Duration1)
290 Integer DO2 Output on Duration (Seconds) (Digital Outputs >
Duration2)
291 Integer DO State (Digital Outputs > DOState)
292 - 300 Reserved
400 Float Float Temperature Offset
3019 Float FMR Level (FMR Radar > Level)
3021 Float FMR Status (FMR Radar > Status)
3023 Float FMR Measured Level (FMR Radar > Meas. Level)
3025 Float FMR Distance (FMR Radar > Measured Dist.)
3027 Integer FMR Custody Mode
3028 Integer FMR Media Type/Application Parameter (FMR Radar >
Medium Prop.)
3029 Integer FMR Pnt Status (FMR Radar > Pnt Status)
3030 Float Average Temperature (NMT Prothermo > Avg Temp)
3032 Float Vapor Temperature (NMT Prothermo > Vap Temp
3034 Float Temp0 (NMT Prothermo > Elem#01)
3036 Float Temp1 (NMT Prothermo > Elem#02)
3038 Float Temp2 (NMT Prothermo > Elem#03)
3040 Float Temp3 (NMT Prothermo > Elem#04)
3042 Float Temp4 (NMT Prothermo > Elem#05)
3044 Float Temp5 (NMT Prothermo > Elem#06)
3046 Float Temp6 (NMT Prothermo > Elem#07)
3048 Float Temp7 (NMT Prothermo > Elem#08)
3050 Float Temp8 (NMT Prothermo > Elem#09)
3052 Float Temp9 (NMT Pr))othermo > Elem#10