2920 Float & Tape Transmitter 5 Display and Configuration Interface
60 Installation and Operations Manual
Cal Level Calibration Level is used to set (calibrate) the encoder
level.
Note If you enter a decimal value, the 2920 interprets
the measurement as a decimal value and applies the
Level Display Units to format the level. If you enter a
string of numbers separated by a dash (xx - xx - xx), the
2920 applies the format of feet-inches-sixteenths.
Control This parameter is used to enable the +24VDC power
bus. This bus can be used for Active HART, 4-20 input
and 4-20 outputs. The Bus can provide ~50 mA of
current.
Parity Communications Parity. Selections are:
None
Even
Odd
Note This parameter is for MODBUS devices only.
MODBUS Reg MAP Selections are:
2920 Map
GSI Map
Note This parameter is for MODBUS devices only.
Temp Offset Mode Applies 100
° temperature offset to detected value.
Selections are:
No offset
Offset Temp 100
°
Note This parameter is for Mark/Space devices only.
Temp Disp Units Indicates the display units of Temperature. Selections
are:
°F
°C
Data Mode Pulse code format of the Mark/Space message.
Selections are:
Fractional + Temp
Decimal + Temp
20 meters + Temp
30 meters + Temp
Fract. No Temp
Decimal No Temp
20 meters No Temp
30 meters No Temp
Note This parameter is for Mark/Space devices only.
Speed Mode Indicates timing of the message. Selections are:
High
Low
Note This parameter is for Mark/Space devices only.