Liebert® Global Products (LGP) MIB
Enable or disable support for getting and setting data using the Liebert® Global Products MIB.
LGP MIB Traps
Enable or disable support for Liebert® Global Products MIB traps.
NOTE: LGP traps will not be sent unless LGP MIB is enabled.
LGP MIB System Notify Trap
Enable or disable support for the LGP System Notification trap. This is a single trap sent each time an alarm or warning
is added or removed from the conditions table. It provides a text description of the event in a varbind of the trap
message.
NOTE: LGP System Notify traps will not be generated unless the LGP MIB is enabled.
SNMPv3 Engine ID Format Type
Selects method to build the engine ID. Valid values:
MAC Address (default): Engine ID built from the Unity card’s MAC address.
Text: Engine ID built from text entered in SNMPv3 Engine ID Text. See Select SNMPv3 Engine ID Format below .
SNMPv3 Engine ID Text
Text on which the engine ID is built when SNMPv3 Engine ID Format Type is Text.
NOTE: If this field is left blank, the engine ID is built from the Unity card’s MAC address.
Select SNMPv3 Engine ID Format
By default, the Engine ID is automatically generated using the MAC address. Optionally, you can select a text based ID instead.
1. Touch , then > BMS & Teamwork > IS-Unity
Setup > Protocols > SNMP.
2. Select the format. Refer to SNMP Protocol Setup on the previous page , for descriptions of the settings and
options.
In SNMPv3 Engine ID Format Type, select MAC Address or Text.
If you selected Text, type the text on which the generated engine ID will be based.
Click Save to confirm the changes or Cancel to discard them.
The new engine ID is not displayed until after rebooting the card in Step 3 .
The text generated engine ID is a hexadecimal representation of ASCII characters similar to that shown in
Figure 8.4 on the next page .
NOTE: If the format type or text for the Engine ID are incomplete or invalid, the Engine ID is generated based on the
MAC Address.
3. Restart Unity:
a. Touch , then > BMS & Teamwork > IS-Unity
Settings.
b. Touch Restart IS-Unity., then touch Yes.
8 External Monitoring andBuilding ManagementSystems
147
Vertiv™ Liebert® iCOM™Installer/User Guide