Mechanical Installation
• A certain type of POE lubricant that is directly supplied by Vertiv must be used, otherwise the compressor
may get damaged. When charging the refrigeration system with oil, consult Vertiv representative for more
details on adding the lubricant oil.
• Adding inferior or incorrect type of lubricant oil will damage the system, so the problems caused due to
quality are not covered by the warranty.
• Do not use inferior quality refrigerant.
• For any consequences resulting from inferior quality refrigerant, Vertiv does not assume warranty
responsibility. Select the type of lubricant oil in accordance with the compressor manufacturer’s
specification.
2.11. Mechanical Installation Checklist
Following are the particulars in the checklist (refer Table 2-12) that need to be verified and confirmed to ensure
that the mechanical installation is implemented successfully.
Table 2-12 Installation Inspection Checklist
Particulars Results
Leave enough space around the unit for maintenance.
Ensure the installation fasteners have been fixed firmly.
The pipes between the indoor and outdoor units have been connected, and the
service valves of the indoor and outdoor units have been opened completely.
The drain pipe has been connected.
All pipe joints tightened.
Irrelevant things (such as transportation material, structure material, and tools) inside
or around the unit have been cleared after the unit is installed.