Vertiv™ | Liebert® SRC-G | User Manual 45
Start-up Commissioning
4.2.2. Dehumidifying
Adjust the humidity setpoint to 10% lower than the indoor relative humidity. Then the control system triggers the
dehumidification demand. Note that during the testing process, if the indoor temperature is 3 ºC higher than the
temperature setpoint, the system may enter in ‘Forced Cooling Mode’ and the dehumidification demand will not
be responded.
Restore the humidity setpoint to the default or the original value after the test.