Vertiv™ | Liebert® SRC-G | User Manual 64
Controller Operation Instructions
Work Mach
This option represents total number of working units in the batch. Rest of the units are considered as standby.
Rotate Mn and Reset Run Mn
Scheduling is achieved by setting rotation min using parameter “Rotate Mn”. This parameter is factory set using
“Reset Run Mn”.
Cas Mode
Cas Mode is selected by “ON”. Cascading mode is activated when Cas Temp is reached. This mode is auto turned
O when once Cas Di is achieve.
STBY BLWR
The status of evaporator fans of standby units can be selected using “STBY BLWR”.