Vertiv | NetSure 7100 Series -48V DC Power System Installation Manual (IM582127000) | Rev. BB
24
Placing the Enclosures, Bolting Enclosures Together, and Securing the Enclosure(s) to the
Floor (if applicable)
System components are factory mounted in a relay rack, on shipping rails, or in an enclosure as specified when
ordered.
Systems Installed in an Enclosure
The system consists of one to six bays. Locate enclosures in a line adjacent to each other, with no space
between them. Place the List 1 Main Bay at the right or left side end, then the List 7 Supplemental Bay, then the
List 8 Supplemental Bay (if furnished), etc. Refer to the following procedures.
Ventilation Requirements
Refer to the General Requirements” on page 16.
Enclosure Floor Mounting Dimensions
Refer to Figure 5 for enclosure floor mounting dimensions.
Figure 5:
Enclosure Floor Mounting Dimensions