Vertiv | NetSure 7100 Series -48V DC Power System Installation Manual (IM582127000) | Rev. BB
157
Control Bus Connections between Controller and Module Mounting Assemblies Spec. No.
588705400
Each Spec. No. 588705400 module mounting assembly in the system is daisy-chained to the controller.
Controller CAN Bus connectors are located at the left and right rear of each shelf. These connectors are used
to interconnect the shelves to the controller and to other shelves. In expansion shelves, these connectors are
factory jumpered so both connectors can be accessed from the center of the shelf. Refer to Figure 73 for
connector locations and an interconnect diagram. These connections are factory made for shelves factory
installed. The connection must be made if a rectifier field expansion shelf is installed as shown in Figure 73.
For field expansion, refer to the procedure in Power System User Instructions UM582127000.