Vertiv | NetSure 7100 Series -48V DC Power System Installation Manual (IM582127000) | Rev. BB
74
Table 3:
SM-DU Switch Settings (cont’d on next page)
DIP Switch S1
Communication
Address
Shunt
Voltage
Shunt
Current
Description of Status
1
2
3
4
5
6
7
8
OFF
OFF
OFF
NA
Address 8#
OFF
OFF
ON
Address 1# (Setting for SM-DU in 1st Supp. Bay)
OFF
ON
OFF
Address 2# (Setting for SM-DU in 2nd Supp. Bay)
OFF
ON
ON
Address 3# (Setting for SM-DU in 3rd Supp. Bay)
ON
OFF
OFF
Address 4# (Setting for SM-DU in 4th Supp. Bay)
ON
OFF
ON
Address 5# (Setting for SM-DU in 5th Supp. Bay)
ON
ON
OFF
Address 6#
ON
ON
ON
Address 7#
NA
OFF
OFF
NA
Shunt Voltage: 75mV
OFF
ON
Shunt Voltage: 25mV (Note 1)
ON
OFF
Shunt Voltage: 50mV
ON
ON
Shunt Voltage: 60mV
NA
OFF
OFF
OFF
Shunt Current: 500A (Note 1)
OFF
OFF
ON
Shunt Current: 100A
OFF
ON
OFF
Shunt Current: 200A
OFF
ON
ON
Shunt Current: 300A
ON
OFF
OFF
Shunt Current: 400A
ON
OFF
ON
Shunt Current: 1000A
ON
ON
OFF
Shunt Current: 1500A
ON
ON
ON
Shunt Current: 2000A
Note 1: Setting for this system.

Table of Contents

Other manuals for Vertiv NetSure 7100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv NetSure 7100 Series and is the answer not in the manual?

Vertiv NetSure 7100 Series Specifications

General IconGeneral
BrandVertiv
ModelNetSure 7100 Series
CategoryPower Supply
LanguageEnglish

Related product manuals