7.6 Vitocell 340-M, type SVKC and Vitocell 360-M, type SVSB
For storing heating water and providing DHW heating in con-
junction with solar collectors, heat pumps and solid fuel boilers
Suitable for the following systems:
■ DHW temperature up to 95 °C
■ Heating water flow temperature up to 110 °C
■ Solar flow temperature up to 140 °C
■ Operating pressure on the heating water side up to 3 bar
(0.3 MPa)
■ Operating pressure on the solar side up to 10 bar (1.0 MPa)
■ Operating pressure on the DHW side up to 10 bar (1.0 MPa)
■
Total water hardness of up to 20 °dH (3.6 mol/m
3
)
Note
Type SVKA without solar heat exchanger.
Specification
Type SVKC/SVSB SVKC/SVSB
Cylinder capacity l 750 950
Heating water content l 708 906
DHW capacity l 30 30
Solar indirect coil capacity l 12 14
DIN registration number
– Vitocell 340-M 9W262-10MC/E
– Vitocell 360-M 9W263-10MC/E
Dimensions
Length (7)
– Incl. thermal insulation a mm 1064 1064
– Excl. thermal insulation mm 790 790
Width b mm 1119 1119
Height
– Incl. thermal insulation c mm 1900 2200
– Excl. thermal insulation mm 1815 2120
Height when tilted
– Excl. thermal insulation and adjustable feet mm 1890 2165
Weight of Vitocell 340-M
– Incl. thermal insulation kg 199 222
– Excl. thermal insulation kg 171 199
Weight of Vitocell 360-M
– Incl. thermal insulation kg 208 231
– Excl. thermal insulation kg 180 208
Connections (male thread)
Heating water flow and return R 1¼ 1¼
Cold water, DHW R 1 1
Heating water flow and return (solar) G 1 1
Drain R 1¼ 1¼
Solar indirect coil
Heating surface
m
2
1.8 2.1
DHW indirect coil
Heating surface
m
2
6.7 6.7
Standby heat loss
To EN 12 897: 2006
Q
ST
with 45 K temperature differential
kWh/24 h 2.25 2.45
Standby capacity V
aux
l 346 435
Solar capacity V
sol
l 404 515
Energy efficiency class — —
DHW cylinders
(cont.)
VITOSOL
VIESMANN
65
5822 440 GB
7