116
wallaceperimetersecurity.comPhone: 866.300.1110
TROUBLESHOOTING
Common Faults
Error Descripon Cause/Soluon
F�212
External Stop circuit #2 In the operator terminals 3 and 4 are for the external stop
circuit #2. These terminals are used for the manual brake
disconnect. There is a N.C. limit switch that is tripped
when the manual brake disconnect is used. Make sure the
manual brake disconnect is released on the corresponding
column.
If you are sll seeing the error, check for the following:
‒ The wires in terminals 3 and 4 are not seated
properly.
‒ The wires in the N.C. limit switch are not seated
properly.
‒ There is a short in the wire.
This error would be tripped by the brake disconnect switch
on FEIG Gen I (i.e., SpeedGate models introduced prior to
2021).
F�369
Sensing Edge Fault Either there is an obstrucon tripping the sensing edge or
the operator was not parameterized properly.
The following parameters must be set to the indicated
values:
P�460 = 0
P�462 = 2
If this sll does not clear the error the wiring or sensing
edge might have become damaged and must be replaced.
F.530
Temperature Fault The operator is below the operang temperature of -10°C
(14° F).
The operator(s) enclosure(s) will either require a heater or
a thermal blanket.
NOTE: This seng can oponally be turned OFF.
F.752
Encoder Fault The encoder has an internal fault and must be replaced. If
the replacement of the encoder does not clear the error,
the encoder cable must also be replaced.
NOTE: On rare occasions the circuit board may be
defecve.