78
wallaceperimetersecurity.comPhone: 866.300.1110
UL 325 MONITORING REQUIREMENT FOR EXTERNAL ENTRAPMENT PROTECTION DEVICES
UL 325 Monitoring Requirement for External Entrapment
Protecon Devices
In accordance with the UL 325 standard, aer July 31st, 2018, all bi-fold gate operators will need a minimum
of 2 external entrapment sensors (1 open direcon and 1 close direcon) installed before automac
operaon is allowed, but all potenal entrapment zones must be protected or eliminated.
ALL external entrapment protecon sensors including non-contact (Photo Eyes) and contact (Edge) sensors
must be monitored, and the operator must verify the presence of every device at least once during each
open and close cycle.
Terminal 40 in the SpeedGate operator enclosure terminal strip is designated for monitoring of all external
entrapment sensor connecons by looking for NC contacts connected to input terminals and cycling the
power.
Addional sensor inputs, if required, can be made available by installing addional blocks on the I/O
expansion board.
Upon monitoring, should any device not be present, or a fault condion occur that precludes the sensing
of an obstrucon, including an interrupon of the wireless signal to the wireless device or an open or short
circuit in the wiring that connects the external entrapment device to the operator and the device’s supply
source, the operator shall funcon with constant pressure for the direcon of travel being protected, or
shall only be able to be moved manually.
The gate operator monitors the “presence” of each entrapment protecon sensor. When the operator no
longer detects a sensor, it will cease automac operaon in the direcon of the missing or failed sensor.
Qualied personnel must be physically present at the site of the gate system to troubleshoot monitoring
faults. If a fault in the entrapment protecon system is detected, fault number 928 will appear on the
boom le of the operator panel LCD diagnosc display. Refer to “F.928” on page 126 for troubleshoong
details.
When the fault or error is resolved, a normal command for a new open or close cycle will restore gate
operaon.
Prior to resuming normal operaon, it is the sole responsibility of the user to ensure the area is free of
obstrucons and that it is safe to operate the gate.