Programme unit
Temperature hysteresis
Here you determine a default value for the
machine’s temperature hysteresis.
The temperature hysteresis can be programmed
individually for each wash program. However,
under certain circumstances, e.g. when the user
has set the temperature manually, the PCU may
not be able to find the temperature hysteresis
values in the current wash program. That is when
it needs to use the default value stored here.
What is temperature hysteresis?
Once the drum has filled with water to the right
level, it is heated to the wash temperature you
have programmed. During the wash the water
will cool down somewhat.
When the water temperature has reached a
lower limit, heating restarts and the water tem-
perature is brought back up to the correct level.
Temperature hysteresis is the number of de-
grees between the wash temperature and the
temperature at which heating needs to restart.
HEATING RELAY ON IF NOT HEATED Y
TEMPERATURE INCREASE ALLOWED Y
LEVEL EMPTY 90
LEVEL OVERFILL 200
PAUSE TEST LEVEL 0
PAUSETESTTEMPERATURE -18°C
DEFAULT TEMPERATURE HYSTERIS 4 °C
TEMPERATURESTEPINCOOL-DOWN 4°C
DEFAULT LOW EXTRACT TIME 00:00
DEFAULT MEDIUM EXTRACT TIME 00:00
DEFAULT HIGH EXTRACT TIME 00:00
DEFAULT DRAIN TIME 00:00
DEFAULT DISTR. TIME 00:00
DO UNBALANCE MEASUREMENT N
DRAIN OPEN DELAY 0:13
START EXTRACT TIME 00:30
1 2 3
4 5 6
7 8 9
0
Use the numeric keys to
enter the value.
If you make a mistake while
entering digits:
Press ERASE.
When you have finished:
Press .
HEATING RELAY ON IF NOT HEATED Y
TEMPERATURE INCREASE ALLOWED Y
LEVEL EMPTY 90
LEVEL OVERFILL 200
PAUSE TEST LEVEL 0
PAUSE TEST TEMPERATURE -18 °C
DEFAULT TEMPERATURE HYSTERIS 4 °C
TEMPERATURESTEPINCOOL-DOWN 4°C
DEFAULT LOW EXTRACT TIME 00:00
DEFAULT MEDIUM EXTRACT TIME 00:00
DEFAULT HIGH EXTRACT TIME 00:00
DEFAULT DRAIN TIME 00:00
DEFAULT DISTR. TIME 00:00
DO UNBALANCE MEASUREMENT N
DRAIN OPEN DELAY 0:13
START EXTRACT TIME 00:30
1 2 3
4 5 6
7 8 9
0
Test values for pause
Here you determine whether, and if relevant, the
conditions under which it will be allowed for the
user to open the door during a wash program, for
example to take samples of the water.
The following conditions must be fulfilled before it
will be possible to open the door:
•TheusermusthavepressedPause.
•Thewaterlevelmustnotexceedthelevelpara-
meter you have programmed as PAUSE TEST
LEVEL.
•Thetemperaturemustnotexceedthetempe-
rature you have programmed as PAUSE TEST
TEMPERATURE.
If one or both of the parameters above is set at
0, this function will be disabled and it will not
be possible to open the door during the wash
program.
Use the numeric keys to
enter the values.
If you make a mistake while
entering digits:
Press ERASE.
When you have finished:
Press .
Wash temperature
Temperature
hysteresis
Heating restarts at
this temp.
Water temperature
Time
Temperature