CLS200 Series User’s Guide
Chapter 6: Ramp/Soak
124
Last Segment
Specify whether the current segment is the last one in the profile.
ALARM
A SEGMENT 01
LAST SEGMENT? NO
Selectable values: NO or YES.
Repeat Cycles
Set the number of times you want a profile to repeat or cycle.
The profile returns to START mode after completing the number of cycles specified here.
ALARM
A REPEAT CYCLES
? 1
Selectable values: 1 to 99, or C (continuous cycling).
Setpoints and Tolerances for Various Input Types
Setpoints and tolerances are set in segments before the profile is assigned to a particular loop.
When the profile is used with a loop, the INPUT TYPE and DISP FORMATS settings are applied to
the following parameters:
• Ready setpoint
• Segment setpoint
• Segment tolerance
Refer to Table 6.3 to determine how these parameters are affected for the various INPUT TYPE and
DISP FORMAT settings.
Table 6.3 — Display Formats
INPUT TYPE DISPLAY FORMAT
YOU ENTER IN
THE PROFILE
RESULTING VALUE WHEN PROFILE IS
ASSIGNED TO A LOOP
Thermocouples
and RTDs
N/A 300 300.0
Linear -999 to 3000 300 300.0
-9999 to 30000 300 300.0
-999.9 to 3000.0 300 300.0
-99.99 to 300.0 300 30.00
-9.999 to 30.000 300 3.000
-9999 to 3.0000 300 0.3000