CLS200 Series User’s Guide
Chapter 3: Using CLS200
54
ALARM
Failed Sensor
Alarm Code
Description
03 T/C BREAK
FS 25MAN 0
Figure 3.7 Failed Sensor Alarm in the Single Loop Display
Alarms that still exist but have been acknowledged are displayed on the Bar Graph display. A letter
or symbol indicates the alarm condition. See Table 3.3 for a full list of alarm codes, failed sensor
messages and alarm symbols.
ALARM
01 F 08
AAAA MAMA
Open
Low Process
or Low Deviation
on Loop 5
on Loop 1
Thermocouple
Figure 3.8 Alarm Symbols in the Bar Graph Display
Table 3.3 shows the symbols used in each form of the alarm display.
Table 3.3Alarm Type and Symbols
ALARM
CODE
BAR GRAPH
SYMBOL
ALARM
MESSAGE
DESCRIPTION
FS F
T/C
BREAK
Failed Sensor: Break detected in thermocouple circuit.
RO F RTD OPEN
RTD Open: Break detected in RTD circuit.
RS F
RTD
SHORTED
RTD Short: Short detected in RTD circuit.
RT F
REVERSED
TC
Reversed Thermocouple: Reversed polarity detected in
thermocouple circuit.
ST F
T/C
SHORTED
Shorted Thermocouple: Short detected in thermocouple
circuit.
HP >
No
message
High Process Alarm: Process variable has risen above the
high alarm set point.
HD >
No
message
High Deviation Alarm: Process variable has risen above the
setpoint plus the deviation alarm value.
LP <
No
message
Low Process Alarm: Process variable has dropped below
the low alarm set point.
LD <
No
message
Low Deviation Alarm: Process variable has dropped below
the setpoint minus the deviation alarm value.
AM *
No
message
Ambient Warning: Controller’s ambient temperature has
exceeded operating limits by 5°C.