Chapter 4: Setup
84
Setup Loop Outputs Menu
Use the SETUP LOOP OUTPUTS menu to:
Enable or disable outputs
Set output type
Set cycle time for time proportioning outputs
Enter Serial DAC parameters (for Serial DAC outputs)
Select control action
Set output level limit and limit time
Select sensor fail output (output override)
Select a nonlinear output curve
ALARM
SETUP LOOP 01
OUTPUTS ?
Table 4.11 shows the parameters available in the SETUP LOOP OUTPUTS menu. Both heat and
cool outputs have the same parameters; only one of each parameter is shown.
Table 4.11Setup Loop Outputs
PARAMETER DEFAULT VALUE
HEAT CONTROL OUTPUT? ENABLED
HEAT OUTPUT TYPE? TP
HEAT OUTPUT CYCLE TIME? 10s
SDAC MODE?* VOLTAGE
SDAC LO VALUE?* 0.00 VDC
SDAC HI VALUE?* 10.00 VDC
HEAT OUTPUT ACTION? REVERSE
HEAT OUTPUT LIMIT? 100%
HEAT OUTPUT LIMIT TIME? CONT
SENSOR FAIL HT OUTPUT? O%
HEAT T/C BRK OUT AVG? OFF
HEAT OUTPUT? LINEAR
COOL CONTROL OUTPUT? DISABLED
*
The SDAC parameters are available only if you select SDAC as the output type.
Use these parameters to configure the Serial DAC signal output.