CLS200 Series User’s Guide
Chapter 4: Setup
86
Heat or Cool Cycle Time
Set the cycle time for time proportioning outputs.
This parameter appears only if the heat or cool output type for the loop is set to time proportioning
(TP).
ALARM
01 HEAT OUTPUT
CYCLE TIME? 10s
Selectable values: 1 to 255 seconds.
SDAC Mode
Select the Serial DAC output signal.
ALARM
01 SDAC MODE?
VOLTAGE
Selectable values: CURRENT or VOLTAGE.
SDAC Low Value
Set the low output signal level for the Serial DAC. The Serial DAC converts 0% output from the
controller to the value set here.
Set the high and low values to match the input range of the output device. For instance, if the output
device has a 0.00 - 10.00 V range, set the SDAC LO VALUE to 0.00 VDC and set the SDAC
HI VALUE to 10.00 VDC.
ALARM
01 SDAC LO VALUE?
0.00 VDC
Selectable values: 0.00 to 9.00 VDC or 0.0 to 19.90 MA. This value must be less than the
SDAC HI VALUE.
SDAC High Value
Set the high output signal level for the Serial DAC. The Serial DAC converts 100% output from the
controller to the value set here.
Set the high and low values to match the range of the output device. For instance, if the output
device has a 4 to 20mA range, set the SDAC HI VALUE to 20.00 MA and the SDAC LO VALUE
to 4.00 MA.