CLS200 Series User’s Guide
Chapter 4: Setup
75
1
This parameter is available only for the pulse loop (loop 5 on four-channel controller, loop 9 on an eight-channel controller
and loop 17 on a sixteen-channel controller).
2
These parameters are available only if LINEAR is selected for INPUT TYPE.
3
These parameter is available only if INPUT TYPE is set to one of the thermocouple or RTD options.
Input Type
Specify the type of input sensor used on this loop:
• Thermocouple type J, K, T, S, R, B or E.
• RTD 1 or RTD 2.
• Linear input.
• Skip (an input type available for unused loops). Alarms are not detected, and the scanning
display does not show loops that are set to SKIP.
• Pulse input (available only for loop 5 on a four-channel controller, loop 9 on an eight-channel
controller or loop 17 on a sixteen-channel controller).
ALARM
01 INPUT
TYPE ? J T/C
Selectable values: See Table 4.6.
Table 4.6 — CLS200 Input Types and Ranges
INPUT TYPE INPUT RANGE
J T/C
-350 to 1,400˚ F (-212 to 760˚ C)
K T/C
-450 to 2,500˚ F (-268 to 1,371˚ C)
T T/C
-450 to 750˚ F (-268 to 399˚ C)
S T/C
0 to 3,200˚ F (-18 to 1,760˚ C)
R T/C
0 to 3,210˚ F (-18 to 1,766˚ C)
B T/C
150 to 3,200˚ F (+66 to 1,760˚ C)
E T/C
150 to 3,200˚ F (+66 to 1,760˚ C)
RTD1
-148.0 to 572.0˚ F (-100.0 to 275.0˚ C)
RTD2
-184 to 1,544˚ F (-120 to 840˚ C)
PULSE
0 to 2kHz
SKIP
Loop not used.
LINEAR
See Linear Scaling Parameters on page 77.