CLS200 Series User’s Guide
Chapter 4: Setup
75
1
This parameter is available only for the pulse loop (loop 5 on four-channel controller, loop 9 on an eight-channel controller
and loop 17 on a sixteen-channel controller).
2
These parameters are available only if LINEAR is selected for INPUT TYPE.
3
These parameter is available only if INPUT TYPE is set to one of the thermocouple or RTD options.
Input Type
Specify the type of input sensor used on this loop:
Thermocouple type J, K, T, S, R, B or E.
RTD 1 or RTD 2.
Linear input.
Skip (an input type available for unused loops). Alarms are not detected, and the scanning
display does not show loops that are set to SKIP.
Pulse input (available only for loop 5 on a four-channel controller, loop 9 on an eight-channel
controller or loop 17 on a sixteen-channel controller).
ALARM
01 INPUT
TYPE ? J T/C
Selectable values: See Table 4.6.
Table 4.6CLS200 Input Types and Ranges
INPUT TYPE INPUT RANGE
J T/C
-350 to 1,400˚ F (-212 to 760˚ C)
K T/C
-450 to 2,500˚ F (-268 to 1,371˚ C)
T T/C
-450 to 750˚ F (-268 to 399˚ C)
S T/C
0 to 3,200˚ F (-18 to 1,760˚ C)
R T/C
0 to 3,210˚ F (-18 to 1,766˚ C)
B T/C
150 to 3,200˚ F (+66 to 1,760˚ C)
E T/C
150 to 3,200˚ F (+66 to 1,760˚ C)
RTD1
-148.0 to 572.0˚ F (-100.0 to 275.0˚ C)
RTD2
-184 to 1,544˚ F (-120 to 840˚ C)
PULSE
0 to 2kHz
SKIP
Loop not used.
LINEAR
See Linear Scaling Parameters on page 77.