CLS200 Series User’s Guide
Chapter 3: Using CLS200
56
If the job was loaded using digital inputs, the display shows:
ALARM
JOB 3 RUNNING
REMOTELY LOADED
Changing the Setpoint
Select the single loop display for the loop you want to change. Press CHNG SP. This display
appears:
ALARM
01 SETPOINT ?
2F
Press YES to change the setpoint.
Press the up or down keys (YES or NO) to increase or decrease the setpoint value.
Press ENTER to save your changes and return to single loop display.
– or –
Press NO or BACK (without pressing ENTER) to return to single loop display without saving
the new setpoint.
Selecting the Control Status
If you set the control status to AUTO, the controller automatically controls the process according to
the configuration information you give it.
If you set the control status to MAN, you need to set the output level.
If you set the control status to TUNE, the controller performs an autotune and chooses PID
parameters.
NOTE! If the loop outputs are disabled, you cannot toggle between manual and
automatic control. If you try it, the screen shows an error message telling you that the
outputs are disabled, as shown below. Use the SETUP LOOPS OUTPUT menu to enable
the outputs. See Setup Loop Outputs Menu on page 84.
ALARM
MAN/AUTO CONTROL
OUTPUTS DISABLED